SETTLEMENT OF CLAIMS
Owners or former owners of property in the United States and Canada, where Entran II hose is or was installed, may qualify for settlement and may obtain information about a class action settlement for property damage claims involving the hose, including claim forms, at www.entraniisettlement.com, or by calling the Claims Administrator (1-800-254-9222).
Installation and Maintenance Notice to Heatway™ Entran II Systems Users
This information is intended for homeowners or users with Heatway™ Entran II
Radiant Heating Systems in their homes.
Entran II hose, manufactured by Goodyear, is one of many component parts that
were used in Heatway’s (CPS) Radiant Heating Systems from approximately 1989-1993.
Goodyear neither designed nor manufactured the systems.
The vast majority of the more than 10,000 installations throughout the nation
continue to perform satisfactorily. Where, however, the systems have not been properly
designed, installed, operated or maintained, a small number of the systems have been
experiencing problems, including damage to the Entran II hose. These design,
installation, operation and maintenance problems should be corrected.
Goodyear has learned during the course of litigation that Heatway (CPS) never
wrote an installation and maintenance manual for Entran II hose. Many homeowners
have not previously received proper advice concerning the design, installation and
maintenance of their systems. Still other homeowners have improperly been told to
replace systems that are functioning properly and that with proper maintenance will
continue to function for years to come.
The purpose of this document is to summarize accepted practices that, if followed,
will help maximize the useful life of hydronic radiant heating systems.
The document is organized in two parts. The first provides a brief summary of
some steps that a homeowner can quickly and easily take. The second part provides a
more detailed explanation of accepted industry practices and guidelines for the design,
installation, operation and maintenance of hydronic heating systems.
NOTICE
As a legal matter, Heatway (CPS) (and its distributors and installers) – not Goodyear – had and have the obligation to advise system users as to proper system design, installation, operation and maintenance. Goodyear has prepared this document,
containing information it has developed with its experts during the course of litigation
with Heatway (CPS), in an effort to assist in identifying the information that Heatway
(CPS) should have ensured reached all system users, but which it has not. In doing so,
Goodyear expressly reaffirms that it is neither waiving (nor changing) its position that
dissemination of such information was the sole obligation and responsibility of Heatway
(CPS) (and its distributors and installers).
Accepted Industry Practices for Owners of Hydronic Heating Systems
Accepted industry practices and guidelines for the installation, operation and
maintenance of hydronic heating systems include the following:
1. All hydronic systems should be designed by a professional engineer registered in the
state of the installation. A summary of accepted industry practices and guidelines is
attached. If you do not know if a professional engineer designed your system, you
should have either a professional engineer or a master plumber check your system to
see if the attached practices and guidelines have been followed. If they have not been
followed, your system should be corrected. If you have had to replace metal
components in your system, such as boilers, expansion tanks, valves, etc, this is likely
a sign of excessive corrosion and improper installation and maintenance.
2. You should have the system fluid checked on an annual basis to assure that the fluid
has the proper pH (a measure of acidity) and the proper level of corrosion inhibiting
chemicals (and the proper level of glycol if your system uses a water-glycol mix). A
plumbing company or a water treatment company can perform these tests for you.
Please provide them with the attached information.
3. If you wish, you can perform a preliminary check of your system fluid by draining a
few ounces of fluid into a clear plastic or glass container. If the fluid contains visible
sediment, particulate matter, or is dark in color, you should promptly have a plumbing
company or a water treatment company test the fluid and replace or treat it as per the
attached information.
4. You can also perform a preliminary check of the pH of a sample of the fluid. A
standard pH test kit, or test strips can be obtained at any store that carries swimming
pool supplies. It is important that you maintain the system fluid pH between 8.5 –
10.5. If the pH of your system fluid is different, you should promptly have a
plumbing company or a water treatment company test the fluid and replace or treat it
as per the attached information.
5. Your system should have a strainer to screen and trap sediment and particulates. This
strainer should be inspected, at a minimum, at the beginning and end of the heating
season. Any sediment and particulates in the strainer should be removed. If you have
a bypass filter (as recommended by Dow), the filter should be checked and/or
replaced at the intervals recommended by the manufacturer of the bypass filter.
6. Following the attached guidelines will help maximize the useful life of your hydronic
heating system. These include making sure that your system is not operated in excess
of 180º F. The system fluid temperature should typically be maintained in the range
of 100º to 130º F. If your system is operating in excess of this temperature range, you
should have either a professional engineer or a master plumber check your system to
make sure that the practices and guidelines on the following pages have been
implemented. If they have not been followed, the system should be corrected.
Industry Practices and Guidelines for the Design, Installation and Operation of
Hydronic Heating Systems
Maximizing the useful life of hydronic radiant heating systems, including all
components thereof, requires adherence to one fundamental requirement. The systems
must be designed, installed, operated and maintained in accordance with accepted
industry standards and guidelines, as well as various publications by the manufacturer of
the systems -- Heatway (CPS). Adherence to these guidelines, including proper system
fluid treatment, will minimize the potential for corrosion in the system. Corrosion, if left
unchecked, can cause premature failure of all components of a hydronic radiant heating
system, including the Entran II hose.
These recommendations have largely been drawn from industry standards,
guidelines, and recommendations of the system manufacturer, Heatway (CPS), including
the following:
1. ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning
Engineers) Handbook, 1987, HVAC Systems and Applications;
2. ASHRAE Handbook, 1985, Fundamentals;
3. Hydronics Institute, Snow Melting Calculation & Installation Guide, Manual
S-40 (1993) including Technical Topic TT#2A, Anti-freeze in Hydronic Systems;
4. Hydronics Institute, Advanced Installation Guide for Hydronic Heating Systems,
Manual 250 (1991);
5. Radiant Panel Association Standard Guidelines (1997);
6. Bell and Gossett Reprint, Hydronic Systems: Analysis and Evaluation (1968,1969);
7. Bell and Gossett, Hydronic Systems Anti-freeze Design, Bulletin No. TEH-176
(1965);
8. Bell and Gossett, Air Control for Hydronic Systems, Bulletin No. TEH-575 (1966);
9. Uniform Mechanical Code (UMC) (1988);
10. Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989);
11. Heatway’s “Minimizing Corrosion in Hydronic Systems,” by Mike Chiles;
12. Heatway’s “Water Treatment in Hydronic Systems,” by Mike Chiles;
13. Heatway’s “Wet Heat Water Treatment,” A Guide to Hydronic System
Cleaners & Corrosion Proofer;
14. Heatway’s letter of November 14, 1996 to “All Heatway Representatives,
Distributing Wholesalers, and Contractors” re: “Water Quality Analysis Request
Program;”
15. Dow’s “Engineering and Operating Guide for DOWFROST and DOWFROST HD
Inhibited Propylene Glycol-based Heat Transfer Fluid;”
16. Union Carbide’s “Ucartherm Heat Transfer Fluids: Optimum Protection for Heating,
Ventilating, and Air Conditioning Systems;”
17. Union Carbide’s Technical Bulletin: “Dilution of Ucartherm Heat Transfer
Fluid,” form UC-38.
SYSTEM DESIGN AND INSTALLATION
Heatway, in its Twintran Application Manual, stresses the need to “Obey the
Building Codes” and states that “The steps we describe in this manual must not take the
place of local, regional, or national building codes and regulations. You must take the
responsibility to ensure that your work in [sic] in compliance with relevant codes.” It
further advises to “Use Designs from Licensed Professionals.”1. Unfortunately, Heatway
(CPS) did not provide this warning in any Entran II Application Manual, because it never
wrote one. Most of the hydronic radiant heating systems observed to date in which there
is some claim of deterioration of the system and/or the Entran II hose, were not designed
by licensed professionals. Each contains one or more deviations from the following
accepted industry standards and guidelines. These design and installation deficiencies
contribute significantly to corrosion in the system and poor system performance.
1. All of these hydronic systems should be designed by a professional engineer
registered in the state of the installation. Heatway’s own Twintran manuals2. also state
this.
Reason: Hydronic radiant heating systems are not simple. They are complex and
should be designed by a professional engineer experienced with the correct design
of hydronic systems. The wide variation in installed configurations, with
numerous instances of incorrectly installed components, further supports this
concern. It is also likely that the state regulatory licensing agency requires these
systems to be designed by a registered professional engineer.
2. The owner or the owner’s representative must perform proper maintenance of the
system fluid, see discussion at page 6. This is the main recurring system deficiency.
Reason: ASHRAE,3 HI,4. B&G5. and glycol manufacturers (such as Dow6. and Union
Carbide7. ) recommend that the operating fluid be checked annually for pH,
inhibitor level, and concentration of glycol. Heatway (CPS) has also endorsed and
made these same recommendations8. The fluids must be checked regularly in order to maintain proper system operation. In the vast majority of the installations investigated to date, neither
Heatway (CPS) nor the suppliers or the installers of these systems, has educated or
instructed the owners about proper care for the operating fluid in these systems. As the
pH drops and inhibitors are exhausted, the system fluid becomes extremely corrosive,
resulting in accelerated failures of system components. For example, there have been
instances where cast iron boilers have reportedly failed after 5 to 7 years of operation.
ASHRAE cites expected life of cast iron boilers in properly maintained systems to be 30
to 35 years. As this example shows, extreme corrosion is taking place in these systems,
due to the temperature of the fluid, the low pH, loss of inhibitors, and incorrectly installed
system components.
3. The circulating pump(s) in the system should be downstream of the boiler, on the
boiler supply (hot water outlet) pipe.9
Reason: Proper location of the circulating pump, together with proper location of
the expansion tank minimizes introduction of air into the system from any loose
connections. Improper location can contribute to corrosion of the system and can
reduce the percentage of glycol in a glycol-based system.
4. The expansion tank in the system should always be located on the inlet to the pump,
not on the pump discharge.10
Reason: With the expansion tank on the pump discharge, portions of the piping
system operate at less than atmospheric pressure, since the pump head (pressure
differential produced by the pump) subtracts from the pre-charge pressure in the
expansion tank. The expansion tank is the point in the system where no pressure
change occurs whether the pump is operating or not. Since the pumps on these
systems have relatively higher heads than normal circulating pumps, (due the fact
that the hydronic hose has a higher pressure drop per given length than copper
pipe) the pressures on the inlet side of the pump and piping, in systems where the
expansion tank is located on the pump discharge, can be negative with respect to
atmospheric pressure. This increases air entering the system at any locations
where the system pressure is less than atmospheric pressure.
5. The air separator should be located at the inlet to the pump, at the boiler outlet (hot
water supply to the system). A “Spirovent” type of air separator should be used on all
these systems as it has substantially better separation efficiency than the “air scoop”
type of separators that are installed on most of the systems.
Reason: Air separators operate most effectively at the point in the system where air is
easiest to remove. This is at the point where the pressure is the lowest (pump inlet)
and the temperature is the highest (boiler outlet). The “air scoop” type of vent is
nothing more than an enlarged portion of the piping system where air is gathered and
collected, to be vented from the system. The “Spirovent” type of air separator uses
mechanical action of the fluid within the air separator to assist in air removal.
6. Air separators must have automatic air vents installed on them to allow air to
automatically vent from the air separator when it is collected. The vent cap on the air
vent must be loose in order to allow air to escape when the vent discharges.
Reason: If the air vent is not installed or not operating properly, air that is collecting
in the system cannot get out. Air that accumulates in the system can cause air
blockages and, if the system fluid is not properly treated with corrosion proofers, the
air will react with the copper and iron components in the system, causing corrosion
and deterioration of all components of the system.
7. Systems should have high point vents and low point drains.
Reason: When the systems are filled and drained, which is necessary on properly
maintained systems, high point vents and low point drains are needed to assure that
all the air is vented from the system when it is filled. They also allow the system to
be drained completely by allowing air to enter the system when drained from a low
point. In addition, when the system is filled or refilled, air vents allow air to be
vented from the system during filling so air binding of the system does not happen.
Air binding prevents fluid from flowing through the hydronic hose.
8. Dielectric unions should be installed on any copper to iron (or steel) connections in
the system, to prevent electrolytic corrosion of the iron and copper system
components
Reason: Copper and iron (or steel) produce an electric potential between them when
physically connected. If not dielectrically separated, the electric potential causes the
iron or steel components in the system to act as a sacrificial anode, releasing
corrosion products into the system.
9. Strainers should be installed on all systems. Additionally, Dow recommends the use
of bypass filters for removal of foreign solids.11
Reason: A strainer acts as an in-line filter (or screen) to remove foreign products
(such as corrosion products) from a system at a controlled location should periodically open and drain the strainer. If corrosion products are not removed from the system at a controlled location, such as a strainer, they can then circulate throughout the system. At points in the system where the fluid velocities are lower, the
corrosion products can settle out of the liquid and plug circuits in the system. A bypass
filtration system, e.g., polypropylene cartridges with a nominal rating of 20-50 microns,
will remove smaller particulates than would be removed by a standard wye strainer.
10. The system fluid temperature should typically be maintained in the range of 100º to
130º F, with a fluid temperature drop of no more than 20º F. In systems where the boiler
supplies fluid to both in-floor radiant heating and to fin-tube baseboard heating, the
piping system must have a properly operating 3-way or mixing valve present.
Reason: Maintaining fluid temperatures in the above range maximizes the useful
life of a hydronic system. In general, the rate of system corrosion and the rate of
deterioration of system components will increase as the operating temperature of
the system fluid increases. Heatway’s Twintran Application Manual notes as
follows: “A floor heating system, due to its nature, requires a longer period of
time to respond to changes in its thermostat setting. However, once the thermal
mass of the floor is heated, it is usually easy to maintain the desired level of
comfort. Therefore, the most appropriate use of a radiant floor heating system is
where the heated structure is kept at a relatively constant temperature.”12 Heatway
further notes: “Water Temperature Required.” As little as 90º F in well
insulated slab floor homes in moderate weather. Most slabs require a range of
100º to 130º and rarely more than 150º.”13 Heatway also notes: “For residential or
light commercial applications you should keep the surface temperature of the
floor no higher than 85º F.”14 Some homes, however, use the same boiler to supply
system fluid to both a radiant floor heating system (which should typically operate
at 100º to 130º) and to fin-tube radiators, which are often set to operate at 180º to
200º F (i.e., in excess of the maximum 180º F temperature allowed by Heatway’s
warranty). These systems should contain mix valves that mix and reduce the fluid
temperature to the in-floor radiant hose such that its temperature is maintained at
the recommended 100º to 130º and should use copper to transport the higher
temperature fluid to the fin-tube radiator. In instances in which Entran II hose has
been used to connect to a fin-tube radiator, it is not being used as a radiant, or
energy transfer, hose.
11. Hose connections to manifolds should be checked for leakage. If leakage is present,
the connections should be repaired by splicing in a new section of hose and connecting it
to the manifold using a constant tension style clamp.
Reason: In 1992 Heatway (CPS) determined that their method of connecting the hose
to manifolds, using screw clamps, was sensitive to variations in how firmly the
installer tightened the screw clamp. Heatway (CPS) subsequently published
“Installation Guidelines for Field Repairs For Entran Energy Transfer Hose” that call for use of BarbTite
adhesive with Heatway Self Tite clamps (a type of constant tension clamp).15
Heatway currently offers Entran Onix Field Repair Kits through its published
price guide.
SYSTEM FLUID TREATMENT
As indicated above, ASHRAE,16 HI,17 B&G18 and glycol manufacturers (such as Dow19 and
Union Carbide20) all recommend that the operating fluid be checked annually for pH,
inhibitor level, and concentration of glycol (if used). Heatway (CPS) has also endorsed
and made similar recommendations. 21 Failure to properly treat and maintain a hydronic
system can result in rapid, severe damage to system components. Untreated or improperly
treated systems will have elevated levels of copper and iron in the recirculating fluid, due
to corrosion of metal components. This is preventable by using standard industry
practices, as described below.
Non Glycol Systems
(Also applicable to Glycol Systems)
1. Before any system is filled, it should be properly cleaned and flushed using a mixture
of 1 to 2 percent trisodium phosphate. Alternatively, a neutral pH surfactant (detergent)
type cleaner can be used to remove oils and greases.
Reason: As stated by Dow, “New systems are typically coated with oil, grease or
a protective film during fabrication, storage, or construction. Dirt, solder flux, and
welding and pipe scale can also cause problems. Therefore, thorough cleaning of
new systems is recommended. A solution of 1 to 2 percent trisodium phosphate
can be used with water for flushing the system.”22
2. If an inhibited glycol (one that includes corrosion inhibitors) is not used in the
system, the system should be filled with good quality potable water, with an inhibitor
package added to maintain proper pH and to minimize any corrosion.
Reason: It is standard industry practice to maintain low metal ion levels through the
use of effective chemical treatment programs and by employing appropriate
mechanical precautions, such as filtration. A well treated system will typically have
levels of metal ions that are less than 0.1 ppm (mg/L) of Copper, and less than 0.2
ppm (mg/L) of Iron.
3. The system should include a by-pass feeder.
Reason: Use of a by-pass feeder will facilitate adding chemical treatments to the
system fluid, as and when it become necessary, without the need to disassemble
piping or other equipment. In most cases, if there is a filter present (as is
recommended above), it can also serve as a by-pass feeder. The by-pass feeder/filter
can also serve as a convenient point from which fluid samples can be taken for testing
purposes.
4. Check the system fluid on an annual basis to assure that the fluid has the proper pH
and the proper level of corrosion inhibiting chemicals.
Reason: Testing the pH of the system fluid is a quick, easy, and inexpensive
indicator of the health of a hydronic system. Testing for and maintaining the proper
level of corrosion inhibiting chemicals will assure that corrosion in minimized. In
each case the test is simple to carry out and could easily be done by either the
homeowner or a plumber. A pH test may be done using a low cost pH meter (approx.
$70) or using a wet test method that is similar to the type used in maintaining
swimming pool waters. The inhibitor tests are equally simple – taking the form of
drop tests (like those used on swimming pools) or simple “dip strips,” where you put
a strip of paper (similar to pH paper) into the fluid and then compare the color that
develops with a standard. A decrease in the fluid pH indicates a system maintenance
problem.
5. Maintain the system fluid pH between 8.5 – 10.5.
Reason: Maintenance of a pH in this range, using a buffering system based on borate,
morpholine or phosphate, will minimize corrosion of copper and mild steel
components. As a general rule, as the pH goes down (becomes more acidic), the
amount of soluble metal ions increases. The lower pH also has the effect of
accelerating the corrosion process. It is standard industry practice to maintain low
metal ion levels through the use of effective chemical treatment programs and by
employing appropriate mechanical precautions, such as filtration. A well treated
system will typically have levels of metal ions that are less than 0.1 ppm (mg/L) of
Copper, and less than 0.2 ppm (mg/L) of Iron.
6. Examples of products that are commercially available and the type of corrosion
inhibitors used in them are:
Nalco 2536 (Borate/Nitrite/Azole)
Nalco 2820 (Molybdate/Borate/Azole)
Drew DWS 2802 (Nitrite/Borate/Azole)
Drew DWS 2808 (Nitrite/Borate/Azole)
Drew DWS 2818 (Molybdate/Borate/Silicate/Azole)
In addition to these, similar products can be obtained from BetzDearborn, Calgon,
Chemtreet and a large number of other regional companies. Heatway also offers a
corrosion proofer, CP-3. One can find listings for specific local water treatment
companies in the Yellow Pages or equivalent type of phone directories.
Glycol Systems
7. Items 1-6 listed above (Non Glycol Systems) are equally applicable for glycol
systems. Indeed, since glycol breaks down to form organic acids, regular testing to
assure proper pH and the proper level of corrosion inhibiting chemicals is essential.
8. The glycol used in the system should be diluted with water that meets the
recommendations of the manufacturer of the glycol. Typically this requires use of
either distilled or deionized water.
Reason: As noted by Dow, “Water used to dilute DOWFROST fluids must meet
certain minimum standards for purity. Impurities in dilution water can increase metal
corrosion, aggravate pitting of cast iron and steel, reduce the effectiveness of
corrosion inhibitors, increase inhibitor depletion rate, cause formation of scale and
other deposits on heat transfer surfaces, and cause clogging of system components . . .
Distilled or deionized water is recommended.”23
Union Carbide, a large glycol manufacturer, makes similar recommendations in their
technical bulletin “Dilution of Ucartherm Heat Transfer Fluid.”24
9. While one can obtain uninhibited glycol and add the inhibitor separately, the best
approach is to buy glycol from the major suppliers and use it for the initial fill of the
system. Examples of available inhibited glycols included:
Dowfrost or Dowfrost HD(propylene glycol)- Dow
Dowtherm SR-1 (ethylene glycol) - Dow
Ucartherm HTF (ethylene glycol) - Union Carbide
Ucar Foodfreeze (propylene glycol) - Union Carbide
10. If the annual testing of the pH level and the level of inhibitor indicates that either is in
need of adjustment, the fluid should either be drained and the system refilled, or the
fluid should be chemically treated to bring the pH level and the level of the inhibitor
back to acceptable levels. Heatway offers an antifreeze additive, Alphi 11. Also, the
inhibitors listed in the “non-glycol” section can be used to treat glycol containing
systems. Additionally, manufacturers of glycols, such as Union Carbide market their
own proprietary products to re-inhibit glycol systems. For example, Union Carbide
markets the following products:
Ucartherm Inhibitor 1000 - a ferrous metal inhibitor booster
Ucartherm Inhibitor 2000 - a ferrous metal inhibitor and pH booster
Ucartherm Inhibitor 3000 - a yellow metal inhibitor and pH booster
11. In addition to annually checking the pH level and the level of corrosion inhibiting
chemicals in the system fluid, glycol systems should be checked annually to assure
that the percentage of glycol exceeds 20%.
Reason: If the level of glycol is allowed to drop below 20%, there is a greater
potential for biological contamination. Again, the particular manufacturer’s
recommendations should be followed. Dow, for example, states “To ensure
maximum effectiveness for corrosion protection, the inhibitor package is designed for
a minimum 25-30 volume percent concentration of glycol in water.”25
Percent glycol can be determined by the homeowner, or a plumber, using a refractometer (cost
approx. $100) or a glycol tester such as used for a car’s antifreeze (cost approx. $40).
Also a plumber/mechanical contractor could arrange for testing to be done by a water
treatment company, if they did not wish to do it themselves.25 Id.
1 Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989).
2 Id.
3 See, e.g., ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers)
Handbook, 1987, HVAC Systems and Applications; and ASHRAE Handbook, 1985, Fundamentals.
4 Hydronics Institute, Advanced Installation Guide for Hydronic Heating Systems, Manual 250 (1991).
5 Bell and Gossett, Hydronic Systems Anti-freeze Design, Bulletin No. TEH-176 (1965).
6 Dow’s “Engineering and Operating Guide for DOWFROST and DOWFROST HD Inhibited Propylene
Glycol-based Heat Transfer Fluid.”
7 Union Carbide’s “Ucartherm Heat Transfer Fluids: Optimum Protection for Heating, Ventilating, and Air
Conditioning Systems.”
8 See, e.g., Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989) (“Every two years, you should have your fluid tested for any change or else flush the system and re-charge it with a new solution. Use a 2% by weight tri-sodium phosphate in your solution to help maintain proper pH”); Heatway’s “Minimizing Corrosion in Hydronic Systems,” by Mike Chiles, (“Treat the water with a good quality corrosion proofer”).
9 Heatway has also made this recommendation. See, e.g., Heatway’s “Minimizing Corrosion in Hydronic
Systems,” by Mike Chiles, (“Locate Circulators in the Correct Position. Pump into radiant circuits”).
10 Id. (“The primary, or boiler, circulator should not be “pushing” into the “expansion tank”).
11 Dow’s “Engineering and Operating Guide for DOWFROST and DOWFROST HD Inhibited
Propylene Glycol-based Heat Transfer Fluid,” at p. 11 .
12 Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989).
13 Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989).
14 Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989).
15 Heatway’s “Installation Guidelines for Field Repairs For Entran Energy Transfer Hose.”
16 See, e.g., ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers)
Handbook, 1987, HVAC Systems and Applications; and ASHRAE Handbook, 1985,Fundamentals.
17 Hydronics Institute, Advanced Installation Guide for Hydronic Heating Systems, Manual 250 (1991).
18 Bell and Gossett, Hydronic Systems Anti-freeze Design, Bulletin No. TEH-176 (1965).
19 Dow’s “Engineering and Operating Guide for DOWFROST and DOWFROST HD Inhibited Propylene
Glycol-based Heat Transfer Fluid.”
20 Union Carbide’s “Ucartherm Heat Transfer Fluids: Optimum Protection for Heating, Ventilating, and
Air-Conditioning Systems.”
21 See, e.g., Heatway Radiant Floors and Snowmelting, Twintran Application Manual (1989) (“Every two
years, you should have your fluid tested for any change or else flush the system and re-charge it with a new
solution. Use a 2% by weight tri-sodium phosphate in your solution to help maintain proper ph”);
Heatways’s “Minimizing Corrosion in Hydronic Systems,” by Mike Chiles, (“Treat the water with a good
quality corrosion proofer”).
22 Dow’s “Engineering and Operating Guide for for DOWFROST and DOWFROST HD Inhibited Propylene Glycol-based Heat Transfer Fluid.,” at p. 97.
23 Dow’s “Engineering and Operating Guide for DOWFROST and DOWFROST HD Inhibited
Propylene Glycol-based Heat Transfer Fluid,” at p. 9.
24 Union Carbide’s Technical Bulletin: “Dilution of Ucartherm Heat Transfer Fluid,” form UC-38.